PSM4-AR - Multi-Channel Pressure Sensor Indicators

PSM4-AR
- Display pressure range : Depending on pressure type, pressure unit (refer to '▣ Rated Pressure and Max. Display Pressure Range')
- Power supply : 12-24VDC
±10%(ripple P-P: max. 10%)
- Power consumption : Max. 3W
- Current consumption : Max. 100mA (adds 20mA for RS485 communication.)
- Number of input channels : 4 EA
- Environment_Ambient temperature : -10 to 50℃, storage: -20 to 60℃
- Environment_Ambient humidity : 30 to 85%RH, storage: 30 to 85%RH
- Accessories : Bracket
Data sheet Print
Display pressure range | Depending on pressure type, pressure unit (refer to '▣ Rated Pressure and Max. Display Pressure Range') |
---|---|
Power supply | 12-24VDC |
Power consumption | Max. 3W |
Current consumption | Max. 100mA (adds 20mA for RS485 communication.) |
Number of input channels | 4 EA |
Input method | DC4-20mA |
Power for external sensor | 12-24VDC |
Control output_Hysteresis | Min. display interval |
Control output_Repeat error | ±0.1% F.S. ±min. display interval |
Control output_Response time | 2.5ms, 100ms, 500ms, 1000ms |
Control output_Protection circuits | Output short over current protection, reverse power polarity protection circuit |
Display digit | PV display part, SV display part: 4-digit, channel display part: 1-digit |
Display method_Display part | 7-segment LED method ᆞPV display part: red or green ᆞSV display part: green ᆞChannel display part: red |
Display method_Output indicator | 8 (OUT1, OUT2: 4 for each) |
Display accuracy | ±0.1% ±2-digit (at 23 ±5℃) |
Control output and display temperature | 0 to 50℃: ±0.2% F.S. ±2-digit (based on 25℃), -10 to 0℃: ±0.3% F.S. ±2-digit |
Communication | RS485 communication output(Modbus RTU) |
Connection_Input | Sensor connector (for CNE-P04, sold separately) terminal |
Connection_Output | Hirose connector 20-pin (HIF3BA-20D-2.54R, flat cable 20-wire, sold separately) terminal |
Insulation resistance | 100MΩ or more (500VDC megger basis) |
Dielectric strength | 1,000VAC 50/60Hz for 1 min (between power terminal and case), 500VAC 50/60Hz for 1 min (between power terminal and RS485 terminal) |
Vibration | 1.5mm amplitude at frequency of 10 to 50Hzin each X, Y, Z direction for 2 hours |
Environment_Ambient temperature | -10 to 50℃, storage: -20 to 60℃ |
Environment_Ambient humidity | 30 to 85%RH, storage: 30 to 85%RH |
Accessories | Bracket |
Weight | Approx. 108g (approx. 65g) |
※Current consumption: Execpt current consumption of sensor part. When all output LED are ON, it is max. 120mA.
※Power supply for sensor: Do not short +V and 0V of sensor connector. It may cause break inner circuit.
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.
Downloads
- No search results
Used together with
- LINEUP BEST
PSS Series
The PSS series analog pressure sensors feature rectangular design with compact sizes. The pressure sensors are available in analog voltage and analog current models and can be connected directly to HMIs, PCs, and PLCs from various brands. With a wide rated pressure range, the PSS series sensors can be applied in various pressure related applications.
CNE Series
The CNE series sensor connectors can significantly reduce installation work and maintenance time. With a wide range of connectors compatible with diverse cables and connection wiring, the sensor connectors help raise the productivity of industrial systems by making wiring work more convenient and efficient..